Reviews Summary by AI:

Controllers is based around a new control module that includes electronic current sensing
Capacitive touchpad for the control interface to give an increased reliability
Power supply: 230/1/50 single phase
FPC-82241: Single Phase, 230VAC, 0.1 -16Amp, 2 Pumps
FPC-82241-E: Single Phase, 230VAC, 12.0 -18Amp, 2 Pumps
Overloads: 0.1-16amps & 12-18amps
Enclosure size: 400 x 300 x 150mm+

SKU: N/A
Clear

Description

FPC-82241 Control panel consists of the following
* Powder Coated Metal Enclosure, Wall mount, IP56, inner door, 400 x 400 x 200mm
* Main Isolator Switch mounted on side
* Circuit Breaker protected Control Circuit
* Low Voltage Control and Input Circuitry
* Auto/Off/Manual Operation of Pumps via keypad
* Contactors and 0.1-16Amp Range Thermal Overloads for Control and Protection of Pump Motors
* LED Indicator Lights for System Status indication
* 6 hour pump run timer and auto alternation
* Visual and Audible Alarms c/w Mute Switch
* 12Vdc Input for thermostat
* Dual Pump Connection

Functions:
Level control mode – Level empty operation controlled by up to 5 float switches: Low level, duty stop, duty start, standby start and
high level
Pressure control mode – Pressure boost operation controlled by up to 3 pressure switches: Duty start, standby start and low
pressure
Duty sharing and alternation – Duty pump alternates on pump start and after 30 minutes of continuous running in alternation
mode, or 6 hours of accumulated running in recirculation mode
Staggered pump start – Prevents excessive current draw and reduces water surge
Manual pump control – Manual pump mode with optional 5 minute timeout to revert to auto mode
System enable input – Enables and disables the system in auto mode
Static duty mode – No duty alternation, for applications using smaller duty pump that always starts first
Smart chirp mode alarms – Audible alarm automatically silences after 5 minutes if not muted, then chirps every 5 minutes