FPC-82141 BMS One Pump 240Vac IP56 with Inner Door DOL 0.1-16A HydroSTART Controller – Matelec – Sewage And Stomwater
$1,454.00
Auto/Off/Manual Operation of Pump via keypad
Contactor and 0.1-16Amp Range Thermal Overload for Control and Protection of Pump Motor
LED Indicator Lights for System Status indication
Pump : Single Phase, 230VAC, 0.1 -16Amp, 1 Pump + BMS Module providing addition volt free outlets.
Enclosure size: 400 x 400 x 150mm+
- Description
- Additional information
- Downloads
Description
* Powder Coated Metal Enclosure, Wall mount, IP56, inner door, 400 x 400 x 200mm
* Main Isolator Switch mounted on side
* Circuit Breaker protected Control Circuit
* Low Voltage Control and Input Circuitry
* Auto/Off/Manual Operation of Pump via keypad
* Contactor and 0.1-16Amp Range Thermal Overload for Control and Protection of Pump Motor
* LED Indicator Lights for System Status indication
* Visual and Audible Alarms c/w Mute Switch
* 12Vdc Input for thermostat
* Single Pump Connection
FUNCTIONS:
Level control mode – Level empty operation controlled by up to 5 float switches
Pressure control mode – Pressure boost operation controlled by up to 3 pressure switches: Duty start, standby start and low
pressure
Duty sharing and alternation – Duty pump alternates on pump start and after 30 minutes of continuous running in alternation
mode, or 6 hours of accumulated running in recirculation mode
Staggered pump start – Prevents excessive current draw and reduces water surge
Manual pump control – Manual pump mode with optional 5 minute timeout to revert to auto mode
System enable input – Enables and disables the system in auto mode
Static duty mode – No duty alternation, for applications using smaller duty pump that always starts first
Smart chirp mode alarms – Audible alarm automatically silences after 5 minutes if not muted, then chirps every 5 minutes
FAULT PROTECTION:
High level alarm – Alarms after 15 minute delay with auto reset in stormwater mode, or after 1 minute with manual reset only in
sewage mode
Low level protection – Alarms and shuts down pumps on low level, manual reset only
Low pressure protection – Alarms and shuts down pumps if low pressure input is closed for 60 seconds
Prime loss protection – Alarms and shuts down running pumps if there is no flow for 30 seconds
Pump anti-seize protection – Runs pumps periodically during low use to prevent seizing
Pump current sensing – Provides adjustable pump overload, undercurrent and zero current protection
Additional information
Dimensions | N/A |
---|---|
Size | FPC-82141-HR/BMS Single Phase HydroSTART 1 Pump Controller, FPC-82141-LR/BMS Single Phase HydroSTART 1 Pump Controller |