Storm Water Pumps And Control Panel in Brisbane CBD


Project Description

  • June 6, 2019
We recently installed 2 x 11kw storm water pumps with a duty of 30 lps each, soft starters on each pump to avoid water hammer and a water level sensor for accurate pump starting. The original pump system had always caused water hammer and was unreliable due to tangling floats in a very turbulent  underground water tank.
We designed, installed and commissioned the pump system.
PROJECT LOCATION:

Brisbane City

PROJECT TYPE:

Pump Design and Installation